Fireplug
CFPM can also be used between the door and a surface mounted lock
e.g. Rimlatch lock. |
|
Fireplug
Hinge Strips and Lock Protection consist of a 0.5mm thick Firefly
104/105 intumescent paper. Hinge Strips are supplied to a standard
size of 100mm x 35mm. |
|
Under
the action of heat, the Fireplug CFPM insulates the areas around
the hinges and lock slowing the passage of heat through the metal.
This principal is also relevant when installed with other ironmongery
such as, lock striker plate, door closers and pivot plates on
double swing doors. |
|
Fireplug
CFPM has been tested by TRADA to British Standard BS476 part 22,
on 20th April 1993. test No. FR1687, also by Chiltern International
Fire on 19th March 1997 to BS476 Part 22, Test no. FER/F97023.
The test criteria attained results in Fireplug CFPM being acceptable
for 30/30 and 1 hour doors. |
|
HINGE
PROTECTION |
|
Cut
Fireplug CFPM to fit tightly into recess notched out of the door
and door frame. With the CFPM only 0.5mm thick an existing recess
will probably be deep enough to avoid any further notching out.
|
|
LOCK
PROTECTION - Mortice Type |
|
Remove
the mortice lock from the door. Some shaving of the door may be
required to refit the lock. The Fireplug CFPM can be either wrapped
around the lock or positioned inside the door. Enough room should
be allowed not to tear the paper. |
|
LOCK
PROTECTION - Yale/Rimlatch Type |
|
Remove
the lock and cut Fireplug CFPM to the contours of the lock. Refit
the lock sandwiching the CFPM between the door and the lock. |
|
In
all cases handle spindles, or lock barrels, passing through the
door should be wrapped in CFPM. Door closers, striker plates and
pivot plates on double swing doors should also have Fireplug CFPM
fitted. |
| |
|
FIREPLUG
CFPM behind hinges |
| |
| To ask questions or
receive information about Fireplug Hinge & Lock Protection,
please use the form below. |
| |
|
| |
|